Development of EMC Filter In the High Powered Breaker |
Eun-Mi Kim1, Mi-Hwa Jeon1, Dong-Il Kim1, Young-Sup Ahn2 |
1Dept. of Radio Sciences & Engineering, Korea Maritime University 2Dept. of Electronics & Comm. Engineering, Mokpo National Maritime University |
|
|
Abstract |
Remarkable developments in the electric and electronic industry have given people's daily life much more convenience and abundance. However, in electrical communication, or electric and electronic fields, making electrical and electronic devices more functional, more integrated, and faster have put electromagnetic interference(EMI) into more complex forms, and lots of problems such as interruption, malfunction, or interference by noise between electrical communication systems occurs every day. In this research, the electromagnetic compatibility(EMC) filter in the high powered breaker was designed and fabricated as a counter measure. The filter attenuated noise more than 20${sim}$50 dB in the range of 10 MHz${sim}$1.5 GHz. And, when the electric fast transient(EFT) of 4 kV in the level 4 of IEC 61000-4-4 was induced, it was soon suppressed to 600 V. |
Key words:
EMI Filter, EMC Filter, Feed-Through Capacitors, Ferrite Beads |
|